Description and Instructions

Description and Instructions The LED Knock-Out Conversion KITS Instructions & Installation for 2'X4', 1'X4', 2'X2' Troffers, Type: Parabolic, Prismatic, Wrap, Surface Mount fixtures and Strip Lights.

KIT # 1 for troffers & wrap

KIT # 2 for strip lights

Tools needed to convert

Custom size available of KIT #1

Custom size available of KIT #2

LED Knock-Out KITS = K-O GiveNewLife for your Troffers & Strip Lights Troffers & Wraps:

                Custom size available

Strip Lights: For 8ft / 4ft/ 2ft fixtures


Custom size available

Those new Knock-Out LED Conversion KITS are a game changer for all your existing of billion of fixtures like the Troffers, Wrap and Strip lights by (GiveNewLife) to your existing lightings system to Convert to LED Tubes with the Knock-Out KITS making it the most energy saving Technology, Economic available in the world for today and tomorrow.

 



3-MODEL size: KITS # 1 Above


      2-MODEL size: KITS # 2 Above

Specifications>> For only TYPE "B" one end power LED tubes:

 

WARNING - Risk of fire or electric shock. LED Knock-Out retrofit Kits installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.

 

WARNING - Risk of fire or electric shock. Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.

 

WARNING – Only those open holes indicated in the photographs and/or drawings may be made or altered as a result of the kit installation. Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation

 

WARNING – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.

 

WARNING –To avoid potential fire or shock hazard, do not use this retrofit kit in luminaires employing shunted bipin lamp holders. Note: Shunted lamp holders are found only in fluorescent luminaires with Instant-Start ballasts. Instant-start ballasts can be identified by the words “Instant Start” or “I.S.” marked on the ballast. This designation may be in the form of a statement pertaining to the ballast itself, or may be combined with the marking for the lamps with which the ballast is intended to be used, for example F40T12/IS. For more information, contact the LED luminaire retrofit kit manufacturer.

 

“THE RETROFIT KIT IS ACCEPTABLE AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY UL OR AUTHORITIES HAVING JURISDICTION.” For cUL units.

 

Safety Caution:

 

One (1)lamp holder will be powered to the electrical coming into the fixture which will transfer the power to the # 14 wiring inserted into the PVC bar. That will activate any other lamp holder added into the PVC bar to provide as much light as needed, up to 4 LED type "B" tubes. Knock-Out KITS model: #1 for Troffers, Wrap and #2 for Strip Lights

Parts Included in this Kit:

1- Power bar.3,2,1 - un-shunted lamp holders.
4 - Robertson self taping screws.
1 - Luminaire quick disconnect.
1- PVC sliding bar.
3,2,1 - PVC T8 clip.
1- Cable tie

KITS number 1 & 2: showing electrical channel toward lamp holders; and securing channel in front.

Installation Instructions:

1. Ensure that power to the existing fixture is off. (Turn Circuit Breaker off) 
2. Open fixture lens. 
3. Remove existing lamps. (T8 or T12 fluorescent tubes)
4. Remove wire cover. Lamp holders and Lamp holder brackets at both ends of fixture. 
5. Disconnect input wires to existing ballast and remove. (Cut the Line and Neutral from ballast, same for remaining wires) At this point you should have an empty fixture body with no components. 
6A. Position the Lamp holder with wire near nearest to the wire cover. 
6B. Insert the power (Line to pin 1 and Neutral to pin 2 coming from the fixture) into the 4 port side of the luminaire quick disconnect making sure to match the colors on the Luminaire Disconnect with the wire color.

7. Screw the pre-drill power bar with self taping screw supply with the kit against one end of troffer closest side to the power entrance in the fixture. 
7A. Secure the accessible wirings between the lamp holder and the wire cover every 100 mm (4 in) to a structural part of the luminaire.

8. Screw the PVC bar on opposite side of fixture and line-up the PVC clips to match the lamp holder use.
9A. Connect the Luminaire Disconnect together.
9B. Secure wiring 10. Re-install the wire and connection cover. 
10. Install LED tubes type "B" with powered end of tube in the powered bar lamp holders. 
11. Install the Caution Label below.
12. Close the fixture lens.
13. Turn on the power.

Type "B" LED Tubes and the most economical of them all (no ballast):

Instruction of the Removal and Installation Diagrams: 2X4 troffer

2X2 troffer

1X4 troffer

Wrap around

KIT #2 INSTRUCTION & INSTALLATION FOR STRIP LIGHTS

Strip Light Conversion KIT

STAY CONNECTED WITH iLIGHTECH CANADA

Search

Location

Contact us

Address: London, ON, Canada

Email: Info@ilightechcanada.com

Phone Number: (226)-213-6328

 

Send an Inquiry